UST Program - LG 113

UST Program - LG 113

Issue Date: October 2, 2003
Revision Date: July 6, 2006
 

INCON Intelligent Controls, Inc.

TS-LS300 Series
(Originally listed as Campo/Miller LS300-120 PLUS AL, LS300-120 PLUS AL A/S, LS300-120 PLUS AL LSI)
(for Rigid and/or Flexible Piping)

AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this leak rate and pressure were certified using an equivalent leak rate and pressure, in accordance with an acceptable protocol.
Leak Threshold 1.5 gph for leak rate of 3.0 gph.
0.1 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuels, fuel oil #4, waste oil, kerosene. 
Other liquids may be tested after consultation with the manufacturer.
Specification System tests pressurized rigid or flexible pipelines for all leak rates.
System tests pressurized combination rigid and flexible pipelines for 3.0 gph leak rate only.
Tests are conducted at operating pressure.
Pipeline Capacity For 3.0 gph leak rate test:
Maximum of 396.6 gallons for rigid pipelines.
Maximum of 95.5 gallons for flexible pipelines.
Maximum of 492.1 gallons for combination of rigid and flexible pipelines (rigid portion cannot exceed 396.6 gallons and flexible portion cannot exceed 95.5 gallons).
For 0.2 leak rate and 0.1 gph leak rate tests:
Maximum of 163 gallons for rigid pipelines (Example: 350 feet of 3 3/8 inch line).
Maximum of 39.5 gallons for flexible pipelines(Example: 430 feet of 1 ½ inch line).
Waiting Time None between delivery and testing. 
None between dispensing and testing for leak rate of 3.0 gph. 
Minimum of 3 hours between dispensing and testing for leak rate of 0.2 gph. 
Minimum of 6 hours between dispensing and testing for leak rate of 0.1 gph.
Test Period Response time is 10 minutes for leak rate of 3.0 gph. 
Minimum of 25 minutes for leak rate of 0.2 gph. 
Minimum of 34 minutes for leak rate of 0.1 gph. 
Test data are acquired and recorded by a microprocessor.
System Features Permanent installation on pipeline. 
Automatic testing of pipeline every 45 minutes for leak rate of 3.0 gph. 
Automatic testing of pipeline when pump has been idle for 3 hours for leak rate of 0.2 gph. 
Automatic testing of pipeline when pump has been idle for 6 hours for leak rate of 0.1 gph. 
Preset threshold.
Triplicate testing to determine if pipeline is leaking. 
Pump shutdown, indicator light and alarm activation if leak is declared.
Calibration

System must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions.

Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions.

 

INCON Intelligent Controls, Inc.

Evaluator:  Ken Wilcox Associates

74 Industrial Park Rd.

Tel:  (816) 443-2494

Saco, ME 04072

Date of Evaluation:  06/23/95, 09/10/98, 05/26/06

Tel: (800) 872-3455

 

E-Mail:  webadmin@incon.com  
URL:  www.incon.com  