Issue Date: April 18, 1997
Revision Date: May 21, 2003
 

Beaudreau Electronics, Inc. Models 404, 406 Liquid Level Sensors with Models 500, 500C Controllers,
Model 522 Remote Monitoring System, and Model 522T Monitoring System
 
LIQUID-PHASE INTERSTITIAL DETECTOR

 

Detector:

Output type qualitative
Sampling frequency continuous
Operating principle float switch (Model 404), refractive index of liquids (Model 406)

Test Results:

Model 404 Liquid Level Sensor

unleaded gasoline

diesel

water

Detection time (sec)

<1

<1

<1

Fall time

manual reset

manual reset

manual reset

Precision (in)

0.0124

0.0167

0.0067

Lower detection limit (in)

0.89

0.72

0.68

Model 406 Liquid Level Sensor  

Detection time (sec)

<1

<1

<1

Fall time

manual reset

manual reset

manual reset

Precision (standard deviation)

0.003474

0.001923

0.005329

Lower detection limit (in)

0.357

0.321

0.369

Specificity Results:
Manufacturer and evaluator claim sensors will respond to any liquid.Manufacturer's Specifications:
Manufacturer states that system requires no calibration.Comments:
Sensors are reusable.

Model 522 Remote Monitoring System:
Evaluation indicates that when threshold level of Model 406 Liquid Level Sensor was reached, Model 522 Remote Monitoring System produced (1) an audible and visual alarm and (2) an output signal that was recognized by a Veeder-Root TLS-350 Monitoring System.
The TLS-350 Monitoring System produced an alarm within 10 seconds, and displayed and printed a notice of alarm and alarm time.
Manufacturer states that the output signal produced by Model 522 Remote Monitoring System can be recognized by other monitoring systems designed to detect this output signal.
Model 522 Remote Monitoring System was evaluated only using the Veeder-Root TLS-350 Monitoring System.

Model 522T Monitoring System:
Evaluation indicates that when threshold level of Model 406 Liquid Level Sensor was reached, Model 522T Monitoring System will generate a visual (LCD readout and LED “alarm” lamp) and audible alarm and also open up to three normally closed relay contacts.
By using a Model 522R Relay, the system can use these normally closed relay contacts to control power to turbine pumps. Alternatively, the normally closed relay contacts can be used to send fuel alarm information to a Veeder-Root TLS-350 for both positive shutdown and additional alarm notification (such as a printout showing the date and time that a release has occurred).
 

Beaudreau Electronics, Inc.
23 Industrial Drive
Waterford, CT  06285-9715
Tel:  (860) 443-6570

Evaluator:  Ken Wilcox Associates
Tel:  (816) 443-2494
Date of Evaluation:  07/20/94
(Revised 09/23/02 & 12/23/02)

 