Issue Date: January 11, 2001
Revision Date: December 21, 2005

PID Analyzers, LLC

(originally listed as HNU Systems, Inc.)

PI-101 with 11.7 EV Probe #101397, HW-101 with 11.7 EV Probe #170214, ISPI-101 with 10.2 EV Probe #111100, DL-101 with 10.2 EV Probe #167085

Out-of-Tank Product Detector (Vapor-Phase)

Detector

Output Type Quantitative
Sampling Frequency Intermittent
Operating Principle Photoionization detector

Test Results

  Unleaded Gasoline Synthetic Gasoline JP-4 Jet Fuel
PI-101
Accuracy* (%) - average reading 29.1 (730 ppm) 12.3 (884 ppm) 29.6 (737 ppm)
Detection time* (sec) 31 21 26
Fall time* (sec) 52 14 49
Lower detection limit (ppm) 14.2 11.7 29.7
HW-101
Accuracy* (%) - average reading 12.6 (888 ppm) 8.5 (1076 ppm) 5.7 (953 ppm)
Detection time* (sec) 20 25 24
Fall time* (sec) 49 10 49
Lower detection limit (ppm) 31.8 21.1 26.8
ISPI-101
Accuracy* (%) - average reading 63.6 (360 ppm) 59.1 (415 ppm) 70.8 (300 ppm)
Detection time* (sec) 20 21 35
Fall time* (sec) 40 10 37
Lower detection limit (ppm) 2.3 5.8 5.1
DL-101
Accuracy* (%) - average reading 63.3 56.2 59.5
Detection time* (sec) 45 22 51
Fall time* (min:sec) 01:03 00:14 01:01
Lower detection limit (ppm) 11.0 5.8 5.0

*For tests conducted with 1000 ppm of test gas

Specificity Results

Activated: n-hexane, toluene, xylene(s)

  • PID Analyzers, LLC
    25 Walpole Park South Drive
    Walpole, MA 02081
    Tel: (508) 660-5001
  • Evaluator: Carnegie Mellon Research Institute
    Tel: (412) 268-3495
    Date of Evaluation: 02/5/92, 02/5/92, 03/5/92, 11/28/91

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.