Issue Date: August 23, 1999
Revision Date: May 28, 2008
Mass Technology Corp.
Precision Mass Measurement Systems SIM-1000 and CBU-1000 (48 hour test)
Bulk Underground Storage Tank Leak Detection (50,000 Gallons or Greater)
Certification | Leak rate is proportional to product surface area (PSA). For tanks with PSA of 6,082 ft², leak rate is 0.294 gph with PD = 95% and PFA = 5%. For other tank sizes, leak rate equals [(PSA in ft² ÷ 6,082 ft²) x 0.294 gph]. Example: For a tank with PSA = 4,000 ft²; leak rate = [(4,000 ft² ÷ 6,082 ft²) x 0.294 gph] = 0.19 gph. |
---|---|
Leak Threshold | Leak threshold is proportional to product surface area (PSA). For tanks with PSA of 6,082 ft², leak threshold is 0.147 gph. For other tank sizes, leak threshold equals [(PSA in ft² ÷ 6,082 ft²) x 0.147 gph]. Example: For a tank with PSA = 4,000 ft²; leak threshold = [(4,000 ft² ÷ 6,082 ft²) x 0.147 gph] = 0.1gph. A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds the calculated leak threshold. |
Applicability | Gasoline, diesel, aviation fuel, fuel oil #4. Other liquids may be tested after consultation with the manufacturer. |
Tank Capacity | Use limited to single field-constructed vertical tanks. Maximum product surface area (PSA) is 6,082 ft² (approximately 88 ft diameter). Performance not sensitive to product level. |
Waiting Time | Minimum of 1 hour, 6 minutes after delivery or dispensing. Valve leaks and pump drain-back may mask a leak. Allow sufficient waiting time to minimize these effects. Waiting times during evaluation ranged from 62 minutes to 31 hours. |
Test Period | Minimum of 48 hours. There must be no dispensing or delivery during test. |
Temperature | Measurement not required by this system. |
Water Sensor | None. Water leaks are measured as increase in mass inside tank. |
Calibration | Differential pressure sensor must be checked regularly in accordance with manufacturer's instructions. |
Comments | Tests only portion of tank containing product. As product level is lowered, leak rate in a leaking tank decreases (due to lower head pressure). Consistent testing at low levels could allow a leak to remain undetected. Evaluated in a nominal 600,000 gallon, vertical underground tank with product surface area (PSA) of 6,082 ft². |
- Mass Technology Corp.
P. O. Box 1578
Kilgore, TX 75663
Tel: (903) 986-3564
Email: info@mtctesting.com
URL: www.mtctesting.com - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 07/31/06
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.