Issue Date: June 19, 1996
Revision Date: June 1, 2016
OMNTEC Mfg., Inc.
OEL 8000, K-OEL 8000, OEL 8000 II, K-OEL 8000 II OEL 8000 III Series Consoles (Proteus B, K, and X Consoles), (MTG - XX Magnetostrictive Probe, 4 inch dia Floats)
Automatic Tank Gauging Method
Certification | Leak rate of 0.2 gph with PD = 97.5% and PFA = 2.5%. |
---|---|
Leak Threshold | 0.1 gph. A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds this threshold. |
Applicability | Gasoline, diesel, aviation fuel, fuel oil #4, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751. |
Tank Capacity | Maximum of 30,000 gallons. Tanks less than 95% full may be tested. Minimum product level required is based on tank diameter as follows: 48" dia/ min 12"; 64" dia/ min 15"; 72" dia/ min 16"; 96" dia/ min 20"; 126" dia/ min 25"; 132" dia/ min 26". For other tank diameters, consult manufacturer. |
Waiting Time | Proteus Series 8000III: Minimum of 8 hours between delivery and testing. OEL Series: Minimum of 4 hours between delivery and testing. There must be no delivery during waiting time. |
Test Period | Minimum of 4 hours, 30 minutes. Test data are acquired and recorded by the controller. Leak rate is calculated from data determined to be valid by statistical analysis. There must be no dispensing or delivery during test. |
Temperature | Average for product is determined by a probe containing a minimum of 5 thermistors. At least one thermistor must be submerged in product during test. |
Water Sensor | Must be used to detect water ingress. Minimum detectable water level in the tank is 0.055 inch. Minimum detectable change in water level is 0.011 inch. |
Calibration | Probe must be checked and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments | Not evaluated using manifolded tank systems. Therefore, this certification is only applicable when there is a probe used in each tank and the siphon is broken during testing. California regulations require at least one test per month after routine product delivery or when the tank is filled to within 10% of the highest operating level of previous month. |
- OMNTEC Mfg., Inc.
1993 Pond Rd.
Ronkonkoma, NY 11779
Tel: (631) 981-2001
Email: omntec@omntec.com
Website: www.omntec.com - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluation: 01/17/96, 09/15/97, 10/26/00 , 3/20/14
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.