Issue Date: July 18, 2016
OMNTEC Mfg., Inc.
Controller Models OEL 8000 III Series (Proteus B, K, and X Consoles) with Liquid level sensors BX-PDS, BX-PDWF, BX-PDWS, BX-LS, BX-LV, BX-LWF, BX-RES
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative, discriminating (PD-PDS, BX-PDWF, and BX-PDWS) others non-discriminating |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Operating principle: optical sensor (all), electrical conductivity (PD-PDS, BX-PDWF, and BX-PDWS) |
Test Results
Unleaded Gasoline | E85 | Diesel | Water | |
---|---|---|---|---|
BX-PDS (Discriminating sensor) | ||||
Detection time (sec) | <1 | -- | <1 | <1 |
Fall time (sec) | <1 | -- | <1 | <1 |
Lower detection limit (in) | 0.7222 | -- | 0.7192 | 0.7122 |
BX-PDWF (Discriminating sensor) | ||||
Detection time (sec) | <1 | -- | <1 | <1 |
Fall time (sec) | <1 | -- | <1 | <1 |
Lower detection limit (in) | 0.2081 | -- | 0.2093 | 0.2102 |
BX-PDWS (Discriminating sensor) | ||||
Detection time (sec) | <1 | -- | <1 | <1 |
Fall time (sec) | <1 | -- | <1 | <1 |
Lower detection limit (in) | 0.7222 | -- | 0.7192 | 0.7122 |
BX-LV | ||||
Detection time (sec) | <1 | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 | <1 |
Lower detection limit (in) | 0.2380 | 0.2417 | 0.2474 | 0.2424 |
BX-LS | ||||
Detection time (sec) | <1 | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 | <1 |
Lower detection limit (in) | 0.5542 | 0.5506 | 0.5689 | 0.5404 |
BX-LWF | ||||
Detection time (sec) | <1 | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 | <1 |
Lower detection limit (in) | 0.2043 | 0.2063 | 0.2044 | 0.2061 |
BX-RES | ||||
Detection time (sec) | <1 | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 | <1 |
Low level threshold - lower detection limit (in) | 2.1418 | 2.1496 | 2.1470 | 2.1425 |
High level threshold - lower detection limit (in) | 13.1819 | 13.1850 | 13.1886 | 136.1813 |
Comments
Manufacturer claims sensors will respond to any liquid after its threshold is exceeded.
Manufacturer claims all sensors can easily be removed, cleaned, and reinstalled if an alarm is triggered or for periodic testing
- OMNTEC Mfg., Inc.
1993 Pond Rd.
Ronkonkoma, NY 11779
Tel: (631) 981-2001
Email: omntec@omntec.com
Website: www.omntec.com - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluation: 04/09/14
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.