Issue Date: November 14, 1997
Revision Date: October 18, 2002
OPW Fuel Management Systems
(originally listed as Emco Electronics, Tuthill Transfer Systems)
EECO 1500, 2000, 3000, Leak Sensor, Leak Sensor II, Leak Sensor Jr. with Q0002-001, Q00002-005 Sensors
Out-Of-Tank Product Detector (Vapor-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Adsistor (Q0002-001sensor), metal oxide semiconductor (Q0002-005 sensor) |
Test Results
Unleaded Gasoline | Synthetic Gasoline | JP-4 Jet Fuel | |
---|---|---|---|
Q0002-001 Sensor | |||
Accuracy* (%) | 100 | 100 | |
Detection time* (min:sec) | 19:32 | 09:16 | |
Fall time* (hh:mm:ss) | 00:32:30 | >01:05:33 | |
Lower detection limit (ppm) | 1000 | 500 | Q0002-005 Sensor |
Accuracy* (%) | 100 | 100 | 100 |
Detection time* (min:sec) | 00:30 | 00:28 | 01:01 |
Fall time* (hh:mm:ss) | 03:34 | 02:40 | 05:33 |
Lower detection limit (ppm) | 100 | 100 | 100 |
*For tests conducted with 1000 ppm of test gas.
** See Glossary
Specificity Results (in addition to above)
Activated: n-hexane, toluene, xylene(s).
Comments
Q0002-001 sensor is not for use with synthetic gasoline.
- OPW Fuel Management Systems
6900 Santa Fe Dr.
Hodgkins, IL 60525
Tel: (708) 485-4200
URL: www.opwglobal.com/opw-fms - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluation: 11/12/96, 10/18/96
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.