Issue Date: November 7, 2001
Revision Date: October 18, 2002
OPW Fuel Management Systems
(originally listed as Petro Vend, Inc.)
SiteSentinel Controller with Single Float Switches Part #30-3221-1, #30-3221-1A, #30-3221-1B Brine Reservoir Sensor and Dual Float Sensor Part #30-3221-2
Out-of-Tank Product Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Float switch |
Test Results
Unleaded Gasoline | Diesel | Water | |
---|---|---|---|
Part #30-3221-1 | |||
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
Lower detection limit (in) | 1.225 | 1.171 | 1.123 | Part #30-3221-1A |
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
Lower detection limit (in) | 1.513 | 1.487 | 1.375 | Part #30-3221-1B |
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
Lower detection limit (in) | 0.876 | 0.828 | 0.562 | Part #30-3221-2 (Brine Reservoir Sensor) |
Detection time (sec) | - | - | <1 |
Fall time (sec) | - | - | <1 |
Lower detection limit (in) | |||
Low level alarm | - | - | 2.495 |
High level alarm | - | - | 2.495 | Part #30-3221-2 (Dual Float Sensor) |
Detection time (sec) | - | - | <1 |
Fall time (sec) | - | - | <1 |
Lower detection limit (in) | |||
Low level alarm | - | - | 2.533 |
High level alarm | - | - | 10.492 |
Specificity Results
Evaluator indicates that single float sensors work with any liquid.
Comments
Evaluator indicates that Sensor Part #30-3221-2 can operate either as a brine reservoir sensor or a dual float sensor based on orientation of the lower float.
- OPW Fuel Management Systems
6900 Santa Fe Dr.
Hodgkins, IL 60525
Tel: (708) 485-4200
URL: www.opwglobal.com/opw-fms - Evaluator: Underwriters Laboratories, Inc.
Tel: (847) 272-8800
Date of Evaluation: 12/10/92
Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluation: 8/3/00
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.