Issue Date: November 22, 1995
Revision Date: April 18, 1997
PermAlert
PAL-AT Models AT20C, AT50C, AT40K with PHL Hydrocarbon Sensor
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Electrical conductivity |
Test Results
Unleaded Gasoline | |
---|---|
Response time (min) | 1.13 |
Recovery time (min) | 8.83 |
Product activation height (cm) | 0.53 |
Lower detection limit (cm) | 0.38 |
Specificity Results (in addition to above)
Activated: synthetic gasoline, diesel, heating oil #2.
Not activated: water.
Comments
Sensors are reusable.
- PermAlert
6410 W. Howard St.
Niles, IL 60714
Tel: (847) 966-2235
Email: marketing@permalert.com
URL: www.permalert.com - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 02/05/92
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.