Issue Date: December 21, 2005
PID Analyzers, LLC
(originally listed as HNU Systems, Inc.)
Model 102 Photoionizer
Out-of-Tank Product Detector (Vapor-Phase)
Detector
Output Type | Quantitative |
---|---|
Sampling Frequency | Intermittent |
Operating Principle | Photoionization Detector |
Test Results
Unleaded Gasoline | Synthetic Gasoline | JP-4 jet fuel | |
---|---|---|---|
Accuracy* (%) - average reading | 85 (423 ppm) | 112.8 (1125.2 ppm) | 8.1 (78.2 ppm) |
Detection time* (sec) | <120 | 11 | 12 |
Fall time* (sec) | <120 | 38 | 11 |
Lower detection limit (ppm) | Not Reported | 2.1 | 5.8 |
*For tests conducted with 1000 ppm of test gas
Specificity Results
Activated: Activated: n-butane, n-hexane, iso-butane, 3-methylpentane, toluene
- APID Analyzers, LLC
25 Walpole Park South Drive
Walpole, MA 02081
Tel: (508) 660-5001 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 10/29/04
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.