Issue Date: April 18, 1997
Revision Date: November 25, 2015
Pneumercator Company, Inc.
LC 1000 Series, E-14-29, E-700-1, LDE-700, LDE-740, TMS 2000, TMS 3000 with Level Sensor Models LS600AB, RSU800
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Float Switch |
Test Results
LS600AB
Unleaded Gasoline | Diesel | Water | |
---|---|---|---|
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
Lower detection limit (in) | 3.32 | 3.28 | 3.18 |
RSU800 (low level)
Unleaded Gasoline | Diesel | Water | |
---|---|---|---|
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
Lower detection limit (in) | 2.57 | 2.53 | 2.31 |
RSU800 (high level)
Unleaded Gasoline | Diesel | Water | |
---|---|---|---|
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
Lower detection limit (in) | 13.31 | 13.24 | 13.01 |
Specificity Results
Manufacturer claims sensors will respond to any chemically-compatible liquid having a viscosity below 1500 cps, provided liquid does not have sticky or gummy properties.
Manufacturer's Specifications
Sensors are reusable.
- Pneumercator Company, Inc.
1785 Expressway Drive North
Hauppauge, NY 11788
Tel: (800) 209-7858, (631) 293-8450 x112
URL: www.pneumarcator.com - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 01/22/96, 01/14/10
(Revised 03/02/01)
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.