Issue Date: November 22, 1995
Revision Date: January 11, 2001

Pneumercator Company, Inc.

LDE 700, LDE 740, LDE 9000 with Sensor Probe Models 9-901, 9-902, 9-903

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Capacitance

Test Results

  Unleaded Gasoline Synthetic Gasoline
Detection time (sec) <1 <1
Lower detection limit (cm)
9-901 0.32 0.36
9-902 0.36 0.36
9-903 0.76 0.74

Specificity Results (in addition to above)

Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.

Comments

Sensors are reusable.
Capacitance probes do not work with oxygenated fuels.

  • Pneumercator Company, Inc.
    120 Finn Court
    Farmingdale, NY 11735
    Tel: (631) 293-8450
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 12/14/93

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.