Issue Date: November 22, 1995
Revision Date: January 11, 2001
Pneumercator Company, Inc.
LDE 700, LDE 740, LDE 9000 with Sensor Probe Models 9-901, 9-902, 9-903
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Capacitance |
Test Results
Unleaded Gasoline | Synthetic Gasoline | |
---|---|---|
Detection time (sec) | <1 | <1 |
Lower detection limit (cm) | ||
9-901 | 0.32 | 0.36 |
9-902 | 0.36 | 0.36 |
9-903 | 0.76 | 0.74 |
Specificity Results (in addition to above)
Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.
Comments
Sensors are reusable.
Capacitance probes do not work with oxygenated fuels.
- Pneumercator Company, Inc.
120 Finn Court
Farmingdale, NY 11735
Tel: (631) 293-8450
- Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 12/14/93
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.