Issue Date: November 22, 1995
Revision Date: July 23, 2003
Phoenix Technologies Division of Phoenix Group
(originally listed as Arizona Instrument Corp. and NESCO)
Encompass USF IPAM #17-901
(Ultrasonic Probe #17-9100)
Automatic Tank Gauging Method
Certification | Leak rate of 0.2 gph with PD = 99.94% and PFA = 2.06%. |
---|---|
Leak Threshold | 0.1 gph. A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds this threshold. |
Applicability | Gasoline, diesel, aviation fuel, fuel oil #4. Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer. |
Tank Capacity | Maximum of 15,000 gallons. Tank must be between 50 and 95% full. |
Waiting Time | Minimum of 3 hours between delivery and testing. There must be no dispensing or delivery during waiting time. |
Test Period | Minimum of 6 hours. Test data are acquired and recorded by system's computer. Leak rate is calculated from data determined to be valid by statistical analysis. There must be no dispensing or delivery during test. |
Temperature | Average for product is obtained by a single temperature sensor that measures change in ultrasonic wave velocity. |
Water Sensor | Must be used to detect water ingress. Minimum detectable water level in the tank is 1.86 inches. Minimum detectable change in water level is 0.012 inch. |
Calibration | Temperature sensor and probe must be checked and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments | Not evaluated using manifolded tank systems. Therefore, this certification is only applicable when there is a probe used in each tank and the siphon is broken during testing. California regulations require at least one test per month after routine product delivery or when the tank is filled to within 10% of the highest operating level of previous month. |
- Phoenix Technologies Division of Phoenix Group
2125 South 48th Street, Suite 106
Tempe, AZ 85282
Tel: (877) 890-3808 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 08/22/94
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.