Issue Date: April 18, 1997
Revision Date: July 12, 2017
Simmons
Corp.
SIR
5.7 LM
STATISTICAL
INVENTORY RECONCILIATION TEST METHOD (QUANTITATIVE)
Certification
|
Leak
rate of 0.2 gph with PD > 99.9% and PFA = 0.0%.
Leak rate of 0.1 gph with PD > 99.0% and PFA < 1.0%.
|
Leak
Threshold
|
If
the absolute value of the calculated leak rate (gain or
loss) is less than the leak threshold and the minimum
detectable leak rate is less than or equal to 0.2 gph
(0.1 gph for the 0.1 gph test), the test result is "pass."
If the absolute value of the calculated leak rate is greater
than or equal to the leak threshold, the result is "fail."
If the minimum detectable leak rate exceeds 0.2 gph (0.1
gph for the 0.1 gph test) and the absolute value of the
calculated leak rate is less than the leak threshold,
the test result is "inconclusive."
|
Applicability
|
Gasoline,
diesel new crank oil, used crank oil, aviation fuel, kerosene, waste oil.
Other more viscous liquids may be tested after consultation
with the vendor.
|
Tank
Capacity
|
Maximum
of 60,000 gallons for single tank.
Maximum of 60,000 gallons cumulative capacity for manifolded
tank systems with no more than 5 tanks in system.
|
Data
Requirement
|
Minimum
of 27 days of product level and flow through data.
|
Comments
|
61%
of data sets evaluated were from manifolded tank systems.
17% of data sets evaluated used data collected by Automatic
tank gauges.
Of 41 data sets submitted for evaluation, all were analyzed
with conclusive results.
Median monthly throughput of tanks evaluated was 55,791
gallons.
Leak rates of 0.05, 0.1 and 0.2 gph were used in evaluation.
Data sets evaluated were supplied by evaluator.
|
Simmons
Corp.
|
Evaluator: S.S.G. Associates
|
106
E. Main Street
|
Tel: (662) 234-1179
|
Richardson,
TX 75081-3327
|
Dates
of Evaluation: 10/28/95, 02/15/00
, 09/03/01
|
Tel: (800) 848-8378
|
|
E-mail:
howard.dockery@simmons-corp.com
|
|
URL:
www.simmons-corp.com
|
|
|