Issue
Date: November 22, 1995
Revision Date: November 6, 1997
Soiltest,
Inc.
Soiltest
Ainlay Tank \'Tegrity\' Tester, S-3
VOLUMETRIC
TANK TIGHTNESS TEST METHOD (OVERFILL)
Certification
|
Leak
rate of 0.1 gph with PD = 99% and PFA = 1%.
|
Leak
Threshold
|
0.05
gph.
A tank system should not be declared tight if the test
result indicates a loss or gain that equals or exceeds
this threshold.
|
Applicability
|
Gasoline,
diesel.
|
Tank
Capacity
|
Maximum
of 15,000 gallons.
Tank must be minimum 100% full.
|
Waiting
Time
|
Minimum
of 10 hours between delivery and testing.
Minimum of 2 hours between "topping off" and
testing.
There must be no dispensing or delivery during waiting
time.
|
Test
Period
|
Minimum
of 1 hour, 30 minutes.
Test data are acquired and recorded manually and by a
strip chart recorder.
Leak rate is calculated from last 1 hour, 30 minutes of
test period data.
There must be no dispensing or delivery during test.
|
Temperature
|
Average
for product is determined by a minimum of 3 thermistors.
|
Groundwater
|
Depth
to groundwater in tank excavation backfill must be determined.
If groundwater is above bottom of tank, product level
must be adjusted to provide net pressure of 2-4 psi at
the bottom of tank during test.
|
Calibration
|
Level
sensors must be calibrated before each test in accordance
with manufacturer's instructions.
Thermistors must be checked annually and, if necessary,
calibrated in accordance with manufacturer's instructions.
|
Comments
|
Not
evaluated using manifolded tank systems.
|
Soiltest,
Inc.
|
Evaluator: Law Engineering Industrial Services
|
86
Albrecht Dr., P. O. Box 8004
|
Tel: (800) 672-6601
|
Lake
Bluff, IL 60044-8004
|
Date
of Evaluation: 11/28/90
|
Tel: (800) 323-1242
|
|
|