Issue Date: November 22, 1995
Revision Date: November 19, 2010
Training and Services Corp.
(originally listed as Hasstech)
AcuRite (for Rigid and Flexible Pipelines)
Line Tightness Test Method
Certification | Leak rate of 0.1 gph with PD = 100% and PFA = 0%. |
---|---|
Leak Threshold | 0.01 gph. A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold. |
Applicability | Gasoline, diesel, aviation fuel, fuel oil #4. |
Specification | System tests rigid and flexible pipelines. Tests are conducted at 150% operating pressure. Mechanical line leak detectors shall be removed or manually isolated from the pipeline for duration of test, or a check valve in pump must be manually closed if testing is to be conducted with a mechanical line leak detector in place. |
Pipeline Capacity | Maximum of 150 gallons. |
Waiting Time | Minimum of 6 hours between delivery and testing. Minimum of 30 minutes between dispensing and testing. |
Test Period | Minimum of 30 minutes. Test data are acquired and recorded manually. Manual calculations are performed by the operator on site. |
Calibration | System must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments | Operating instructions include specific procedures for flexible pipelines. Formerly manufactured by Hasstech. |
- Training and Services Corp.
501 Bains St., Suite 113
Brookshire, TX 77423
Tel: (281) 934-3839 - Evaluator: Lamar University
Tel: (409) 880-8788
Date of Evaluation: 03/25/91, 04/02/01
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.