Issue Date:  September 28, 2004
Revision Date: August 8, 2017

Veeder-Root

ILS-350, TLS-300 Series, TLS-450 Series, TLS-4 8601 Series, EMC, EMC-Series, and Red Jacket ProMax, Red Jacket ProPlus
with Single-Point Mini Hydrostatic Sensor 794380-304

INTERSTITIAL DETECTOR (LIQUID-PHASE)


Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

reed switch 

Test Results:

ILS-350, TLS-300 Series, TLS-450 Series, TLS-4 Series, EMC, EMC-Series, and Red Jacket ProMax, Red Jacket ProPlus

Single-Point Mini Hydrostatic Sensor
794380-304

30% by Weight CaCl2

50% by Volume Propylene Glycol

Detection time (sec)

<15

<60

Fall time (sec)

<15

<60

Minimum product level (in)

0.793

0.669

TLS-4 8601 Series
(The TLS-4 8601 Series consists of the following derivatives: TLS-4, TLS-4B, TLS-4c, TLS-4i, and TLS-S1 consoles.)

Single-Point Mini Hydrostatic Sensor
794380-304

30% by Weight CaCl2

50% by Volume Propylene Glycol

Detection time (sec)

<60

*

Fall time (sec)

<60

*

Minimum product level (in)

0.8010

*


*TLS-4 8601 Series testing did not include testing with ethylene glycol . Evaluator expects comparable results from previous testing with other consoles listed.

Comments:
Manufacturer states that Sensor 794380-304 is installed near the bottom of a brine reservoir.  An alarm is triggered if the brine level falls below the threshold level of the sensor.
Manufacturer also states that the sensor withstands removal and replacement from the reservoir without damage to the sensor.
The testing conducted for this evaluation determined the sensor's response to brine only.  The evaluator states that other liquids would also produce an alarm if the sensor threshold is exceeded.  These thresholds would be slightly different for different liquids due to the differing densities.  These liquids, and the threshold for each, have not been determined at this time.

Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.

Veeder-Root
125 Powder Forest Dr.
Simsbury, CT  06070-2003
Tel:  (860) 651-2700
E-mail:  dhalla@veeder.com
URL:  www.veeder.com/dynamic/index.cfm
Evaluator:  Ken Wilcox Associates
Tel:  (816) 443-2494
Date of Evaluation:  05/18/04, 03/03/08, 12/22/16      