Issue Date:
September 22, 2004
Revision Date: March 16, 2015
Veeder-Root
TLS 350, 350PC,
350R, 350RPC, 350Plus, LLD-300, Red Jacket ProMax Leak Detector,
with Series 8484 PLLD and TLS 450 with Series 8590 DPLLD, Software Version X19 or Higher
(for Rigid and/or Flexible Pipelines)
AUTOMATIC ELECTRONIC
LINE LEAK DETECTOR
Certification
|
Leak rate
of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with
PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure*
with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure,
this leak rate and pressure were certified using
an equivalent leak rate and pressure, in accordance
with an acceptable protocol.
|
Leak Threshold
|
1.5 gph
for leak rate of 3.0 gph.
0.17 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds
this threshold.
|
Applicability
|
Gasoline, diesel, aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751*.
Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility - see "Disclaimer".
Evaluations determined that the Series 8484 PLLD responds to 100% Lubrizol Ultrazol 9888, 100% Afton OTR 8332G, and 100% Afton OTR 8843G. Alarm and response can be expected to be very similar to the response values listed above.
|
Specification
|
System
tests pressurized rigid, flexible, and combination
of rigid and flexible pipelines.
Tests are conducted at operating pressure.
System
will not function with a mechanical line leak detector
installed in the pipeline. |
Pipeline
Capacity
|
Maximum
of 119.4 gallons.
|
Waiting Time
|
None between
delivery and testing.
None between dispensing and testing for leak rate of
3.0 gph.
Minimum of 4 minutes to 1 hour, 9 minutes between dispensing
and testing for leak rate of 0.2 gph.
Minimum of 1 to 4 hours between dispensing and testing
for leak rate of 0.1 gph.
|
Test Period
|
Response
time is 1 to 6 minutes for leak rate of 3.0 gph.
Response time is 40 minutes to 227 minutes for leak
rate of 0.2 gph.
Response time is 45 minutes to 333 minutes for leak
rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
|
System Features
|
TLS 350 console can only be used with Series 8484 PLLD.
TLS 450 console can only be used with Series 8590 DPLLD.
When using Red Jacket BIG-FLO Submersible Pump Models P100H1, P200H1, P200H3, P300H3, P500H3, the PLLD only performs 3.0 gph testing and not precision (0.2 and 0.1 gph) testing.
{USER DEFINED} pipe type must be selected under the PLLD setup to allow precision (0.2 and 0.1 gph) testing with Red Jacket BIG-FLO Submersible Pump Models: MAXXUM MXP300, MAXXUM MXP500.
Total vertical rise of pipeline must not exceed 11 feet above transducer.
Permanent installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Pump shutdown (optional), message display and alarm
activation if leak is declared.
|
Calibration
|
System was evaluated on a pipeline consisting of rigid
and flexible piping, and the resulting combined bulk
modulus was determined by physical measurement at evaluator's
facility.
To use this system, a measurement of bulk modulus must
be made at the owner's facility so that the software
can be programmed to deal with the specific characteristics
of the piping system at the facility.
Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions.
|
Veeder-Root
|
Evaluator: Midwest
Research Institute
|
125 Powder Forest Dr.
|
Tel: (816) 753-7600
|
Simsbury, CT 06070-2003
|
Dates of Evaluation:
10/16/95, 01/31/97
|
Tel: (860) 651-2700
|
Evaluator: Ken Wilcox
Associates
|
E-mail: info@veeder.com
|
Tel: (816) 443-2494
|
URL: www.veeder.com
|
Date of Evaluation:
07/20/04, 02/27/08, 7/28/09, 03/24/11(letter), 3/6/2013(letter), 4/4/2015 (letter) |
|