UST Program - LG 113

UST Programs - LG 113

Issue Date: September 11, 1998
Revision Date: September 20, 2011

 

Veeder-Root
(originally listed as Marley Pump Co.)

Red Jacket PPM 4000, RLM 9000, ST 1401L, ST 1801L 
(for Flexible Pipelines)

AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this leak rate and pressure were certified using an equivalent leak rate and pressure, in accordance with an acceptable protocol.
Leak Threshold 0.1 gph for leak rate of 0.2 gph. 
0.05 gph for leak rate of 0.1gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel, methanol and methanol blends, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751*.
Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility - see "Disclaimer".
Specification System tests pressurized flexible pipelines. 
Tests are conducted at operating pressure.
Pipeline Capacity Maximum of 27.6 gallons.
Waiting Time None between delivery and testing. 
None between dispensing and testing.
Test Period Response time is 9 minutes to 2 hours, 30 minutes for leak rate of 0.2 gph. 
Response time is 26 minutes to 4 hours for leak rate of 0.1 gph. 
Test data are acquired and recorded by a microprocessor. 
Calculations are automatically performed by the microprocessor.
System Features Permanent installation on pipeline. 
Automatic testing of pipeline. 
Preset threshold. 
Single test to determine if pipeline is leaking. Recording and display of day, date, and time of conclusive test.
Pump shutdown, message display, and alarm activation if leak is declared.
Calibration Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions.
Comments PPM 4000 is a stand alone automatic electronic line leak detector. 
RLM 9000 is a combination of RLM 5000 automatic tank gauge and PPM 4000 automatic electronic line leak detector. 
ST 1401L is a combination of ST 1400 automatic tank gauge and ST 1401L automatic electronic line leak detector. 
ST 1801L is a combination ST1800 automatic tank gauge and ST 1801L automatic electronic line leak detector.

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT 06070-2003

Dates of Evaluation:  07/28/96, 01/31/97, 03/24/11(letter)

Tel: (860) 651-2700

 

E-mail:  info@veeder.com  
URL:  www.veeder.com  