Issue
Date: September 11, 1998
Revision Date: September 20, 2011
Veeder-Root
(originally listed as Marley Pump Co.)
Red
Jacket PPM 4000, RLM 9000, ST 1401L, ST 1801L
(for Flexible Pipelines)
AUTOMATIC
ELECTRONIC LINE LEAK DETECTOR
Certification
|
Leak
rate of 0.2 gph at operating pressure with PD = 100% and
PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure*
with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this
leak rate and pressure were certified using an equivalent
leak rate and pressure, in accordance with an acceptable
protocol.
|
Leak
Threshold
|
0.1
gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold.
|
Applicability
|
Gasoline, diesel, aviation fuel, methanol and methanol blends, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751*.
Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility - see "Disclaimer".
|
Specification
|
System
tests pressurized flexible pipelines.
Tests are conducted at operating pressure.
|
Pipeline
Capacity
|
Maximum
of 27.6 gallons.
|
Waiting
Time
|
None
between delivery and testing.
None between dispensing and testing.
|
Test
Period
|
Response
time is 9 minutes to 2 hours, 30 minutes for leak rate
of 0.2 gph.
Response time is 26 minutes to 4 hours for leak rate of
0.1 gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
|
System
Features
|
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking. Recording
and display of day, date, and time of conclusive test.
Pump shutdown, message display, and alarm activation if
leak is declared.
|
Calibration
|
Equipment
must be checked annually for capability of detecting a
line leak of 3.0 gph and, if necessary, calibrated in
accordance with manufacturer's instructions.
|
Comments
|
PPM
4000 is a stand alone automatic electronic line leak detector.
RLM 9000 is a combination of RLM 5000 automatic tank gauge
and PPM 4000 automatic electronic line leak detector.
ST 1401L is a combination of ST 1400 automatic tank gauge
and ST 1401L automatic electronic line leak detector.
ST 1801L is a combination ST1800 automatic tank gauge
and ST 1801L automatic electronic line leak detector.
|
Veeder-Root
|
Evaluator: Ken Wilcox Associates
|
125 Powder Forest Dr.
|
Tel: (816) 443-2494
|
Simsbury, CT 06070-2003
|