Issue Date: November 11, 2004
Revision Date: October 27, 2005
Sequence Controls, Inc.
(originally listed as Armstrong Monitoring, Corp.)
AMC 5100
Cable Sensors: AMC 5016 and AMC 5016A
Out-of-Tank Product Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Electrical conductivity |
Test Results*
Diesel | |
---|---|
AMC-5016 | |
Detection time (min:sec) | 20:15 |
Fall time (min:sec) | Not Reported |
Lower detection limit (cm) | 0.04 |
AMC-5016A | |
Detection time (min:sec) | 9:25 |
Fall time (min:sec) | Not Reported |
Lower detection limit (cm) | 0.04 |
*For tests conducted with 0.32 cm of floating product.
Comments
Detection times represent the mean of 5 test periods.
Manufacturer indicates that the sensor cables will detect the presence of petroleum fuels ranging from refined naphtha to heavy crude in bunkers.
The cables are designed to be reusable after being subjected to a petroleum product.
If the sensor cable is subjected to trace amounts of diesel fuel, the cable can be removed and dried in the open air in a matter of hours.
If the sensor cables become supersaturated, the manufacturer recommends and provides a procedure to wash the cables.
The washing procedure is included in the AMC-5016 and 5016A manuals for customers that order diesel or heavy petroleum product detection systems.
- Sequence Controls, Inc.
150 Rosamond Street
Carleton Place, Ontario, Canada K7C 1V2
Tel: (613) 257-7356
E-mail: kvanspengen@sequencecontrols.com
URL: www.sequencecontrols.com - Evaluator: Environment Canada
Tel: (613) 991-1108
Date of Evaluation: 08/27/04
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.