Issue Date: December 5, 2002
Engineering Design Group
Ronan X-76 CTM Automatic Tank Gauging System
(MTS Level Plus UST Probe)
Bulk Underground Storage Tank Leak Detection Method (50,000 Gallons Or Greater)
Certification | Leak rate is proportional to product surface area (PSA).
For tanks with PSA of 564 ft2, leak rate is 0.2 gph with PD > 99.9% and PFA < 0.1%. For other tank sizes, leak rate equals [(PSA in ft2 ÷ 564 ft2) x 0.2 gph]. Example: For a tank with PSA = 846 ft2; leak rate = [(846 ft2 ÷ 564 ft2) x 0.2 gph] = 0.3 gph. Leak rate may not be scaled below 0.2 gph. |
---|---|
Leak Threshold | Leak threshold is proportional to product surface area (PSA). For tanks with PSA of 564 ft2, leak threshold is 0.1 gph. For other tank sizes, leak threshold equals [(PSA in ft2 ÷ 564 ft2) x 0.96 gph]. Example: For a tank with PSA = 846 ft2; leak threshold = [(846 ft2 ÷ 564 ft2) x 0.1 gph] = 0.15 gph. Leak threshold may not be scaled below 0.1 gph. A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds the calculated leak threshold. |
Applicability | Gasoline, diesel, aviation fuel, fuel oil #4. Other liquids may be tested after consultation with the manufacturer. |
Tank Capacity | Use limited to single, field-constructed, vertical-walled tanks having a capacity of 50,000 to 75,000 gallons Maximum product surface area (PSA) is 846 ft2. |
Waiting Time | Minimum of 4 hours, 48 minutes after delivery or transfer. |
Test Period | Minimum of 6 hours. There must be no delivery, transfer, or dispensing during test. |
Temperature | Average for product is determined by five resistance temperature detectors (RTDs) |
Water Sensor | Must be used to detect water ingress. Minimum detectable water level in the tank is 0.874 inch. Minimum detectable change in water level is 0.011 inch. For tanks with a product surface area (PSA) of 564 ft2 and containing 0.874 inches of water, system takes more than 64 days to detect a 0.20 gph water ingress rate. |
Calibration | System must be checked and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments | Tests only portion of tank containing product. As product level is lowered, leak rate in a leaking tank decreases (due to lower head pressure). Consistent testing at low levels could allow a leak to remain undetected. Evaluated in nominal 50,000 gallon tank with PSA of 564 ft2. |
- Engineering Design Group, Inc.
800 Meridian Tower
5100 E. Skelly Drive
Tulsa, OK 74135
Tel: (918) 628- 7100 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 11/16/01
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.