Issue Date: September 1, 2006
Revision Date: April 11, 2016

Franklin Fueling Systems

TS-LS500, TS-LS500E Series
(for Rigid, Flexible or Hybrid Combination of Rigid and Flexible Pipelines)

Automatic Electronic Line Leak Detector

Certification

Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this leak rate and pressure were certified using an equivalent leak rate and pressure, in accordance with an acceptable protocol.

Leak Threshold 1.5 gph for leak rate of 3.0 gph.
0.1 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuels, fuel oil #4, waste oil, kerosene, biodiesel B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751.
Specification On pressurized rigid flexible, or combination rigid and flexible pipelines, system can perform 3.0 gph, 0.2 gph,and 0.1 gph tests.
Tests are conducted at operating pressure.
Pipeline Capacity Maximum of 312.2 gallons for steel and fiberglass pipelines (examples: 480 feet of 4 inch line; 671 feet of 3 3/8 inch line ).
Maximum of 95.4 gallons for flexible pipelines (examples: 260 feet of 3 inch line; 1040 feet of 1 ½ inch line).
Maximum of 415.8 gallons for hybrid combination rigid and flexible pipelines (the capacity of the flexible component cannot exceed 95.4 gallons).
Maximum of 176 gallons for Franklin Fueling Systems UPP semi-rigid pipeline. (example: 513 feet of 3 inch line; 1892 feet of 1 1/2 inch line).
Waiting Time None between delivery and testing.
None between dispensing and testing for leak rate of 3.0 gph.
Depending on temperature stability, 1½ to 10 hours between dispensing and testing for leak rates of 0.2 gph and 0.1 gph.
Test Period Response time is 1 to 2 minutes for leak rate of 3.0 gph.
Minimum of 25 minutes for leak rate of 0.2 gph.
Minimum of 34 minutes for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor.
System Features Permanent installation on pipeline.
Automatic testing of pipeline every 45 minutes for leak rate of 3.0 gph.
Automatic testing of pipeline when pump has been idle for 2 hours for leak rate of 0.2 gph.
Automatic testing of pipeline when pump has been idle for 3½ hours for leak rate of 0.1 gph.
Pump shutdown, indicator light and alarm activation if leak is declared for 3.0 gph and 0.2 gph tests.
The TS-LS500E series is an explosion proof version of the original TS-LS500 series.
Calibration

System must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions.

Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions.

  • Franklin Fueling Systems
    4805 Voges Rd.
    McFarland WI 53558
    Tel: (608) 838-8786
    Email: info@franklinfueling.com
    URL: www.franklinfueling.com
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 06/23/95, 09/10/98, 05/26/06

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.