Issue Date: December 20, 2013
Franklin Fueling Systems
(originally listed as Beaudreau Electric, Inc.)
Model FFS 404-4 Controller with Models S404 and S406 Liquid Level Sensors
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Float switch (Model S404) refractive index of liquids (Model S406) |
Test Results
Unleaded Gasoline | Diesel | Water | Unleaded E85 | Used oil | |
---|---|---|---|---|---|
Model S404 Liquid Level Sensor | |||||
Detection time (sec) | <1 | <1 | <1 | <1 | <1 |
Fall time | <1 | <1 | <1 | <1 | <1 |
Precision (in) | 0.0008 | 0.0014 | 0.0027 | 0.0025 | 0.0029 |
Lower detection limit (in) | 1.154 | 1.1146 | 0.9919 | 1.1324 | 1.1482 |
Model S406 Liquid Level Sensor | |||||
Detection time (sec) | <1 | <1 | <1 | -- | <1 |
Fall time | <1 | <1 | <1 | -- | <1 |
Precision (in) | 0.0017 | 0.0026 | 0.0032 | -- | 0.0027 |
Lower detection limit (in) | 0.5856 | 0.6301 | 0.6884 | -- | 0.6564 |
Specificity Results
This evaluation determined the sensor's responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Manufacturer's Specifications
Manufacturer states that systems require no calibration.
Annual functional test required
Comments
Sensors are reusable.
Franklin Fueling Systems requires their own manufacturer certification for sensor installation and maintenance. Previous manufacturer certifications are not allowed, even if certification is current.
- Franklin Fueling Systems
3760 Marsh Road
Madison, WI 53718
Tel: (800) 225-9787
Email: info@franklinfueling.com
URL: www.franklinfueling.com - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 07/20/94, 10/18/11
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.