Issue Date: April 18, 1997
Revision Date: June 5, 2002

Gems Sensors, Inc.

(originally listed as Warrick Controls, Inc.)

Model DFP-25 Sensor

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Product solubility

Test Results

  Unleaded Gasoline Synthetic Gasoline Water
Detection time (hr:min:sec) 0:06:50 4:14:40 N/A
Fall time** N/A* N/A N/A
Lower detection limit (cm) 2.54 2.54 N/A

*See glossary.

**Fall time is not applicable, since sensor must be replaced after activating.

Specificity Results

Activated: Evaluator claims that this sensor will respond to any material that is capable of dissolving the hydrocarbon-sensitive wax.
Not Activated: Water.

Comments

Sensor is activated when hydrocarbon-sensitive wax is dissolved, releasing a spring that activates an alarm.
Sensor is not reusable, and must be replaced after contact with hydrocarbons.
Liquid level was set at 1 inch (2.54 cm) during test.

The detector is not reusable and must be replaced after contact with hydrocarbons. California regulations require sensors to be tested annually to verify proper operation. This sensor is a self-destruct type and therefore cannot be used in California.

  • Gems Sensors, Inc.
    1 Cowles Rd.
    Plainville, CT 06062-1198
    Tel: (800) 378-1600
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 11/18/96

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.