Issue Date: April 18, 1997
Revision Date: January 27, 2011
Franklin Fueling Systems
(Originally listed as INCON Intelligent Controls, Inc.)
Tank Sentinel TS-1000EFI, TS-1001/TS-2001, and TS-5xxx Series with TSP-DIS BriteSensor; Tank Sentinel TS-1000/TS-2000, TS-1001/TS-2001, and TS-5xxx Series with TSP-EIS Standard Sensor; Tank Sentinel TS-1000/TS-2000 with TSP-PS Liquid Contact Sensor
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Opto-electric |
Test Results
Unleaded Gasoline | Synthetic Gasoline | Diesel Fuel** | Heating oil #2 | Water | E85 | |
---|---|---|---|---|---|---|
TSP-DIS BriteSensor | ||||||
Detection time (min:sec) | 03:13 | 03:17 | 3:00 | 3:02 | 03:18 | -- |
Fall time (min) | <1 | <1 | <1 | <1 | <1 | -- |
Product activation height (cm) | 1.60 | N/D* | N/D | N/D | 1.92 | -- |
Lower detection limit (cm) | 1.60 | 1.60 | 1.50 | 1.50 | 1.62 | -- |
TSP-EIS Standard Sensor | ||||||
Detection time (min:sec) | 03:01 | 03:17 | 3:00 | 3:02 | 03:07 | <1 |
Fall time (min) | <1 | <1 | <1 | <1 | <1 | <1 |
Product activation height (cm) | 1.50 | N/D | N/D | N/D | N/D | 1.99 |
Lower detection limit (cm) | 1.50 | 1.60 | 1.50 | 1.50 | 1.50 | 1.99 |
TSP-PS Liquid Contact Sensor | ||||||
Detection time (min:sec) | 01:14 | 01:13 | 01:10 | 01:16 | 01:25 | -- |
Fall time (min) | <1 | <1 | <1 | <1 | <1 | -- |
Product activation height (cm) | 1.37 | N/D | N/D | N/D | N/D | -- |
Lower detection limit (cm) | 1.22 | 1.21 | 1.20 | 1.24 | 1.32 | -- |
**This evaluation determined the sensor's responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Comments
Comparison of Tank Sentinel TS-1001/TS-2001 and TS-5xxx series consoles with Tank Sentinel TS-1000 (including EFI) /TS-2000 series consoles showed comparable results when evaluated with representative sensors. Sensors are reusable.
- Franklin Fueling Systems
3760 Marsh Road
Madison, WI 53718
Tel: (800) 225-9787
Email: info@franklinfueling.com
URL: www.franklinfueling.com - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 12/09/94, 01/30/96, 07/02/93
Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 4/01/2008
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.