Issue Date: April 18, 1997
Revision Date: June 20, 2008
Franklin Fueling Systems
(Originally listed as INCON Intelligent Controls, Inc.)
Tank Sentinel TS-1000EFI, TS-1001/TS-2001, and TS-5xxx Series with TSP-DDS BriteSensor, TSP-DTS BriteSensor, TSP-MWS BriteSensor Groundwater Probe
Out-of-Tank Product Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Magnetic switch and float (TSP-DDS, TSP-DTS BriteSensor), and hydrocarbon sensitive polymer (all) |
Test Results
Unleaded Gasoline | Synthetic Gasoline | Diesel | Heating oil #2 | Water low level |
Water high level |
|
---|---|---|---|---|---|---|
TSP-DDS BriteSensor | ||||||
Detection time (min:sec) | 05:35 | 06:00 | 38:43 | 38:16 | 06:02 | 06:09 |
Fall time (min:sec) | 34:27 | 28:53 | > 60:00 | > 60:00 | < 01:00 | < 01:00 |
Lower detection limits (cm) | ||||||
Product activation height | 0.50 | N/D* | 3.16 | N/D | N/D | N/D |
Product thickness on water | 0.04 | N/D | N/D | N/D | N/D | N/D |
TSP-DTS BriteSensor | ||||||
Detection time (min:sec) | 06:02 | 05:59 | 38:43 | 38:16 | 06:02 | 06:13 |
Fall time (min:sec) | 22:28 | 28:53 | < 01:00 | < 01:00 | > 60:00 | > 60:00 |
Lower detection limits (cm) | ||||||
Product activation height | 0.50 | N/D | 3.16 | N/D | N/D | N/D |
Product thickness on water | 0.04 | N/D | N/D | N/D | N/D | N/D |
TSP-MWS BriteSensor Groundwater Probe | ||||||
Detection time (min:sec) | 10:13 | 06:42 | ||||
Fall time (min:sec) | 26:52 | 14:43 | ||||
Lower detection limits (cm) | ||||||
Product thickness on water | 0.04 | 0.04 |
Specificity Results (S BriteSensor Groundwater Probe)
Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s).
Comments
Comparison of Tank Sentinel TS-1001/TS-2001 and TS-5xxx series consoles with Tank Sentinel TS-1000(including EFI)//TS-2000 series consoles showed comparable results when evaluated with representative sensors.
Sensors are reusable.
- Franklin Fueling Systems
3760 Marsh Road
Madison, WI 53718
Tel: (800) 225-9787
Email: info@franklinfueling.com
URL: www.franklinfueling.com - Evaluator: Carnegie Mellon Research Institute
Tel:(412) 268-3495
Dates of Evaluation:12/09/94, 02/19/96
Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 4/1/08
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.