Issue Date: November 22, 1995
Revision Date: October 18, 2002
OPW Fuel Management Systems
(originally listed as Emco Electronics, Tuthill Transfer Systems)
EECO System, Leak Sensor II, Leak Sensor Jr. Thermistor and Proximity probes
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Thermal conductivity, proximity switch |
Test Results
Unleaded Gasoline | Synthetic Gasoline | |
---|---|---|
EECO System | ||
Detection time (sec) | <5 | <5 |
Fall time | Manual reset | Manual reset |
Lower detection limit (cm) | ||
Thermistor | 1.22 | 1.12 |
Proximity | 0.97 | 1.04 | Leak Sensor II |
Detection time (sec) | <5 | <5 |
Fall time | Manual reset | Manual reset |
Lower detection limit (cm) | ||
Thermistor | 1.14 | 1.14 |
Proximity | 1.12 | 1.17 | Leak Sensor Jr. |
Detection time (sec) | <5 | <5 |
Fall time | Manual reset | Manual reset |
Lower detection limit (cm) | ||
Thermistor | 1.24 | 1.19 |
Proximity | 1.12 | 1.17 |
Specificity Results
Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.
Comments
Sensors are reusable.
Systems alarm if either water or product leaks into interstitial space.
- OPW Fuel Management Systems
6900 Santa Fe Dr.
Hodgkins, IL 60525
Tel: (708) 485-4200
URL: www.opwglobal.com/opw-fms - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluation: 11/09/92
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.