Issue Date: April 9, 2012

OPW Fuel Management Systems

iSite, iTouch, and EECO Series Fuel Management Systems with OPW Intelligent Sensor (and Company Equivalent):
30-231-S, 30-0230-S (30-3221-1A/1B, Q003-009); 30-0231-L (30-3221-1); 30-0232-D-10/D-20/D-10B/D-20B (Q0003-001/002); and the 924B Sump Sensor

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Float switch

Test Results

  Unleaded Gasoline
E10
Unleaded Gasoline
E15
Unleaded Gasoline
E85
30-0231-S, 30-0230-S (30-3221-1A/1B, Q0003-0009)
Lower detection limit (in) 0.803 0.995 0.942
Detection time (min) <1 <1 <1
Fall time (min) <1 <1 <1
30-0231-L (30-3221-1)
Lower detection limit (in) 1.405 1.518 1.518
Detection time (min) <1 <1 <1
Fall time (min) <1 <1 <1
30-0232-D-10/D-20/D-10B/D-20B (Q0003-001/002)
Lower detection limit (in) 0.02 <0.125 <0.125
Detection time (min) <9 <13.72 <13.72
Fall time (min) <1 <1 <1
924B Sump Sensor
Lower detection limit (in) 4.029 4.029 4.029
Detection time (min) <1 <1 <1
Fall time (min) <1 <1 <1

Specificity Results

Evaluator claims sensors will respond to any liquid.

Comments

Manufacturer and evaluator claim sensors will respond to any liquid after the sensor's threshold is exceeded.

  • OPW Fuel Management Systems
    6900 Santa Fe Dr.
    Hodgkins, IL 60525
    Tel: (708) 485-4200
    URL: www.opwglobal.com/opw-fms
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 5/31/11

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.