Issue Date: November 22, 1995
Revision Date: April 18, 1997

PermAlert

PAL-AT Models AT20C, AT50C, AT40K with PHL Hydrocarbon Sensor

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Electrical conductivity

Test Results

  Unleaded Gasoline
Response time (min) 1.13
Recovery time (min) 8.83
Product activation height (cm) 0.53
Lower detection limit (cm) 0.38

Specificity Results (in addition to above)

Activated: synthetic gasoline, diesel, heating oil #2.

Not activated: water.

Comments

Sensors are reusable.

  • PermAlert
    6410 W. Howard St.
    Niles, IL 60714
    Tel: (847) 966-2235
    Email: marketing@permalert.com
    URL: www.permalert.com
  • Evaluator: Carnegie Mellon Research Institute
    Tel: (412) 268-3495
    Date of Evaluation: 02/05/92

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.