Issue Date: June 17, 2008
PermAlert
LiquidWatch Leak Detection System LW64-IS with PHLR-LW and PHLR-P-LW Hydrocarbon Probes
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Product soluble |
Test Results
Unleaded Gasoline | |
---|---|
Response time (sec) | 24 |
Recovery time (hour) | >16 |
Product activation height (mm) | 2.0 |
Lower detection limit (mm) | 3.9 |
Specificity Results (in addition to above)
Activated: diesel, jet fuel
Not activated: water
Comments
Sensors are reusable.
“PHLR-S/L” sensors are designed for operation in ambient pressure environments while “PHLR-P-S/L” sensors are designed for operation in pressurized environments.
- PermAlert
6410 W. Howard St.
Niles, IL 60714
Tel: (847) 966-2235
Email: marketing@permalert.com
URL: www.permalert.com - Evaluator: Trace Laboratories
Tel: (847) 934-5300
Date of Evaluation: 02/23/07
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.