UST Program - LG 113

UST Programs - LG 113

Issue Date: April 18, 1997
Revision Date: December 6, 2002
 

ProTank, Inc.

UTA-5000 Ullage Tester 
(Vacuum or Pressure Test)

NON-VOLUMETRIC TANK TIGHTNESS TEST METHOD (ULLAGE)

Certification Leak rate of 0.1 gph with PD = 100% and PFA = 0%.
Leak Threshold A tank system should not be declared tight when the acoustic signal detected is different from the baseline. Baseline is the acoustic signal before tank is pressurized or evacuated..
Applicability Gasoline, diesel, aviation fuel, fuel oil #4, waste oil.
Other liquids may be tested after consultation with the manufacturer.
Tank Capacity Maximum ullage volume is 16,500 gallons..
Waiting Time None between delivery and testing
Test Period A few minutes to determine background noise and a leak.
Depends on background noise at the site and on the size of the leak.
After the desired pressure has been reached, the tank should be allowed to settle for 10 minutes.
There must be no dispensing or delivery during test.
Test Pressure Vacuum of 1 psi must be maintained in ullage by a vacuum blower, or total pressure at bottom of tank of 4 psi must be maintained using nitrogen.
Temperature Acoustic signal is independent of product temperature.
Groundwater Depth to groundwater in tank excavation backfill must be determined.
If groundwater is above product level, vacuum test should not be used.
Pressure test may only be used if net pressure can be maintained at a minimum 1 psi throughout ullage during test. If this requires more than 5 psi total pressure at tank bottom, the ullage test must not be used.
Comments Not evaluated using manifolded tank systems.
Evaluated using diesel. Tests only ullage portion of the tank.
Product-filled portion of tank must be tested with an underfill test method.
Microphone was 25 feet away from the leak source during evaluation.
If background noise is too high, test is inconclusive.
Noise signals are tape recorded (not digitally recorded).
Vacuum test method may not be effective in some tank excavation backfill (such as clay) because it may plug holes in tank.
If soil is saturated with product, air or water ingress may not be declared by vacuum test.
A well point in tank excavation backfill may help identify presence of this condition.

 

ProTank, Inc.

Evaluator:  Ken Wilcox Associates

3545 Lomita Blvd., Suite G

Tel:  (816) 443-2494

Torrance, CA  90505

Date of Evaluation:  01/15/93

Tel:  (800) 438-1111

 

   

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.