Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Programs - LG 113

Issue Date:  January 11, 2001

Simone Engineering, Inc.

Magnetrol Model 918 Ultrasonic Point Level Switch with ABB Automation Freelance 2000 Control System

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative, non-discriminating

Sampling frequency:

continuous

Operating principle:

electrical conductivity, ultrasonic

Test Results:

 

trichloroethylene

acetone

water

Lower detection limit (in)

0.143

0.166

0.164

Detection time (sec)

<1

<1

<1

Fall time (sec)

<1

<1

<1

Specificity Results:
Evaluator claims sensors will respond to any liquid after threshold is exceeded.

Comments:
The Magnetrol Model 918 has not been evaluated for application with petroleum hydrocarbons.  The sensor has been evaluated specifically for application in water, acetone, and trichloroethylene.
The ABB Automation Freelance 2000 was used to detect the 8 to 16 milliamp change that occurred in the Magnetrol sensor when it became submerged in product.  Audible and visual alarms were activated when the sensor indicated that alarm conditions were present.

 

Simone Engineering, Inc.

Evaluator:  Ken Wilcox Associates

2635 45th Street

Tel:  (816) 443-2494

Highland, IN 46322-2985

Date of Evaluation:  01/27/00

Tel:  (219) 922-6750

 