Issue Date: November 22, 1995
Revision Date: August 23, 1999

Linde Services, Inc.

(formerly Praxair Services, Inc., originally listed as Tracer Research Corp.)

Tracer Tight

Out-Of-Tank Product Detector (Vapor-Phase)

Detector

Output Type Quantitative
Sampling Frequency Intermittent
Operating Principle Chromatographic (looks for chemical tracer)

Test Results

*California regulations require vadose zone vapor monitoring to be continuous. This sensor does not meet the criteria.

  Xylene Benzene 2-methylbutane Unleaded gasoline Chemical tracers
Hydrocarbon Detector (GC/FID)
Accuracy (%) <20 <20 <20 <20 N/R*
Bias (%) 0 0 0 0 N/R
Detection time (sec) <1 <1 <1 <1 N/R
Fall time (sec) <1 <1 <1 <1 N/R
Lower detection limit (ppm) 20 20 20 20 N/R
Tracer Detector
Accuracy (%) N/R N/R N/R N/R <20
Bias (%) N/R N/R N/R N/R 00
Detection time (sec) N/R N/R N/R N/R <1
Fall time (sec) N/R N/R N/R N/R <1
Lower detection limit (ppm) N/R N/R N/R N/R 10-5

*See glossary.

Manufacturer's specifications

Soil permeability at the site must exceed 1 Darcy.

Comments

System utilizes a chromatographic measurement of a vapor sample collected monthly from the site. Hydrocarbon vapors and the added chemical tracer can be measured independently.
During evaluations, the tracer chemical was declared 159 out of 161 trials.

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.