Certification
|
Leak
rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100%
and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure*
with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this
leak rate and pressure were certified using an equivalent
leak rate and pressure, in accordance with an acceptable
protocol.
|
Leak
Threshold
|
2.5
gph for leak rate of 3.0 gph.
0.136 gph for leak rate of 0.2 gph.
0.068 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold.
|
Applicability
|
Gasoline,
diesel, aviation fuel.
Other liquids may be tested after consultation with the
manufacturer.
|
Specification
|
System
tests pressurized flexible, fiberglass and steel pipelines.
Tests are conducted at operating pressure.
|
Pipeline
Capacity
|
Maximum
of 172 gallons for rigid pipelines.
Maximum of 39.5 gallons for flexible pipelines.
|
Waiting
Time
|
None
between delivery and testing.
None between dispensing and testing.
|
Test
Period
|
Response
time is less than 8 minutes for leak rate of 3.0 gph.
Response time is 1 hour, 48 minutes to 10 hours, 54 minutes
for leak rates of 0.2 and 0.1 gph.
|
System
Features
|
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold. Single test to determine if pipeline
is leaking.
LD-2100 is a stand alone system.
PLC-5000 must be coupled with the 98LD-2000.
Pump shutdown, message display and alarm activation if
leak is declared.
|
Calibration
|
Equipment
must be checked annually for capability of detecting a
line leak of 3.0 gph and, if necessary, calibrated in
accordance with manufacturer's instructions.
|