Issue
Date: August 23, 1999
Revision Date: December 16, 2015
Vaporless
Manufacturing
Vaporless
98LD-2000, 99LD-2000, 99LD-2200, LD-2200 Scout
(for Rigid and Flexible Pipelines)
AUTOMATIC
MECHANICAL LINE LEAK DETECTOR
Certification
|
Leak
rate of 3.0 gph with PD = 100% and PFA = 0%.
|
Leak
Threshold
|
2.5
gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold.
|
Applicability
|
Gasoline,
diesel, aviation fuel.
Other liquids may be tested after consultation with the
manufacturer.
Evaluations determined that the 99LD-2000 MLLD responds to 100% Lubrizol Ultrazol 9888, 100% Afton OTR 8332G, and 100% Afton OTR 8843G. Alarm and response can be expected to be very similar to the response values listed above.
|
Specification
|
System
tests pressurized flexible, fiberglass, and steel pipelines.
Tests are conducted at operating pressure.
|
Pipeline
Capacity
|
Maximum
of 172 gallons for rigid pipelines.
Maximum of 39.5 gallons for flexible pipelines.
|
Waiting
Time
|
None
between dispensing and testing.
None between delivery and testing.
|
Test
Period
|
Response
time is less than 1 minute without a leak and 1 to 8 minutes
with a leak.
|
System
Features
|
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared.
|
Calibration
|
Equipment must be
checked annually for capability of detecting a line leak
of 3.0 gph and, if necessary, calibrated in accordance
with manufacturer's instructions.
|
Comments
|
Functionality and operability
of the 99 LD-2000 and 99 LD-2200 are unchanged by installation
of the Leak Detection Sensor (piston switch) that supports
the VMI ISM-4080 and ISM-4081 Integrated Shutdown Module.
|
Vaporless
Manufacturing
|
Evaluator:
Ken Wilcox Associates
|
8700
East Long Mesa Drive
|
Tel:
(816) 443-2494
|
Prescott
Valley, AZ 86314
|
Dates
of Evaluation: 05/20/98, 11/10/98
, 12/9/15
|
Tel:
(928) 775-5191
|
|
|