Issue Date: November 22, 1995
Revision Date: November 28, 2012

Vaporless Manufacturing

Vaporless 99 LD-3000, LD-3000, 99 LD-3000S, LD-3000S
(for Rigid, Flexible, or Hybrid Combination of Rigid and Flexible Pipelines)

AUTOMATIC MECHANICAL LINE LEAK DETECTOR

Certification Leak rate of 3.0 gph with PD = 100% and PFA = 0%.
Leak Threshold 2.0 gph.
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel.
Other liquids may be tested after consultation with the manufacturer.
Specification System tests pressurized steel and fiberglass pipelines and combination of rigid and flexible pipelines.
Tests are conducted at operating pressure.
Pipeline Capacity Maximum of 404 gallons for steel and fiberglass pipelines
Maximum of 96 gallons for flexible pipelines
Maximum combined capacity is 500 gallons, not to exceed the above individualcapacity limitations for combination rigid or flexible pipelines.
Waiting Time None between dispensing and testing.
Test Period Response time is 9 seconds.
System Features Permanent installation on pipeline.
Automatic testing of pipeline.
LD3000 - restricted flow to dispenser if leak is declared.
LD3000S - pump shutoff if leak is declared.
Calibration Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions.
Comments Functionality and operability of the 99 LD-3000 are unchanged by installation of the Leak Detection Sensor (piston switch) that supports the VMI ISM-4080 and ISM-4081 Integrated Shutdown Module.

 

Vaporless Manufacturing

Evaluator:  Ken Wilcox Associates

8700 East Long Mesa Drive

Tel:  (816) 443-2494

Prescott Valley, AZ 86314

Dates of Evaluation:  08/20/93 , 04/17/06

Tel:  (928) 775-5191

 



 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.