UST Program - LG 113

UST Programs - LG 113

Issue Date: November 22, 1995
Revision Date: September 20, 2011
 

Veeder-Root

TLS-350, 350PC, 350R, 350RPC, 350Plus, Red Jacket ProMax Line Leak Detector, Series 8475 VLLD

AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this leak rate and pressure were certified using an equivalent leak rate and pressure, in accordance with an acceptable protocol.
Leak Threshold 1.5 gph for leak rate of 3.0 gph.
0.1 gph for leak rate of 0.2 gph.
0.079 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751*.
Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility - see "Disclaimer".
Specification System tests pressurized fiberglass and steel pipelines.
Tests are conducted at operating pressure.
System will not function with a mechanical line leak detector installed in the pipeline.
Pipeline Capacity Maximum of 158 gallons.
Waiting Time None between delivery and testing.
Minimum between dispensing and testing depends on volume of product and temperature gradient which is determined by system's computer.
Test Period Response time is 14 seconds for leak rate of 3.0 gph.
Response time is 6 minutes for leak rate of 0.2 gph.
Response time is 14 minutes for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
System Features Permanent installation on pipeline.
Automatic testing of pipeline. Preset threshold.
If pump side leak testing is required, total vertical rise or pipeline must not exceed 8 feet above VLLD Controller.
Single test to determine if pipeline is leaking.
Pump shutdown, message display and alarm activation if leak is declared.
Calibration Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions.

 

Veeder-Root

Evaluator:  Midwest Research Institute

125 Powder Forest Dr.

Tel:  (816) 753-7600

Simsbury, CT  06070-2003

Date of Evaluation:   09/20/91

Tel:  (860) 651-2700

Evaluator:  Ken Wilcox Associates

E-mail: info@veeder.com

Tel:  (816) 443-2494

URL: www.veeder.com

Date of Evaluation:  04/12/93, 03/24/11(letter)