Issue
Date: November 22, 1995
Revision Date: September 20, 2011
Veeder-Root
TLS-350,
350PC, 350R, 350RPC, 350Plus, Red Jacket ProMax Line Leak
Detector, Series 8475 VLLD
(for Flexible Pipelines)
AUTOMATIC
ELECTRONIC LINE LEAK DETECTOR
Certification
|
Leak
rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100%
and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure*
with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this
leak rate and pressure were certified using an equivalent
leak rate and pressure, in accordance with an acceptable
protocol.
|
Leak
Threshold
|
1.5
gph for leak rate of 3.0 gph.
0.1 gph for leak rate of 0.2 gph.
0.079 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold.
|
Applicability
|
Gasoline, diesel, aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751*.
Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility - see "Disclaimer".
|
Specification
|
System
tests pressurized flexible pipelines.
Tests are conducted at operating pressure.
System will not function with a mechanical line leak detector
installed in the pipeline.
|
Pipeline
Capacity
|
Maximum
of 49.6 gallons.
|
Waiting
Time
|
None
between delivery and testing.
Minimum between dispensing and testing depends on volume
of product and temperature gradient which is determined
by system's computer.
|
Test
Period
|
Response
time is 1 minute for leak rate of 3.0 gph.
Response time is 45 minutes to 8 hours, 51 minutes for
leak rate of 0.2 gph.
Response time is 1 hour, 12 minutes to 12 hours, 54 minutes
for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
|
System
Features
|
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
If pump side leak testing is required, total vertical rise of pipeline must not exceed 8 feet above VLLD Controller.
Single test to determine if pipeline is leaking.
Pump shutdown, message display and alarm activation if
leak is declared.
|
Calibration
|
Equipment
must be checked annually for capability of detecting a
line leak of 3.0 gph and, if necessary, calibrated in
accordance with manufacturer's instructions.
|
Veeder-Root
|
Evaluator: Ken Wilcox Associates
|
125
Powder Forest Dr.
|
Tel:
(816) 443-2494
|
Simsbury, CT 06070-2003
|
Date
of Evaluation: 08/04/93, 03/24/11(letter)
|
Tel:
(860) 651-2700
|
|
E-mail: info@veeder.com |
|
URL: www.veeder.com |
|
|