Veeder-Root

Dispenser Pan Sensor 847990-001 and Differentiating Dispenser Pan Sensor 847990-002 with
Dispenser Control Interface

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:         

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

product permeable, reed switch/float

Test Results:
*California requires annual certification of all leak detection equipment. The certification of discriminating sensors should include functional testing of both water and product detection capabilities.

Model 847990-002: This sensor can only respond to liquid directly in contact with the detection element, and is unable to detect a product release floating on an existing pool of water whose height exceeds the level of the detection element.

 

polymer strip

float switch

 

unleaded gasoline

diesel*

water

Dispenser Pan Sensor 847990-001

     

Detection time (sec)

<1

<1

<1

Minimum product level (in)

1.71

1.66

1.62

Precision (in)

0.006

0.004

0.008

Differentiating Dispenser Pan Sensor 847990-002

 

 

 

Minimum product thickness (in)

0.06

0.06

N/A**

Minimum product level (in)

0.03

0.06

6.39

Precision (in)

N/A***

N/A***

0.008

Detection time (min:sec)

06:30

19:50

<00:01

*Evaluations determined these sensors' responses to the liquids shown above and those indicated in the following section. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
**See glossary.
***Tested at discrete levels only.

Specificity Results (in addition to above):
Activated:  synthetic gasoline, n-hexane, toluene, xylene(s)
Not activated:  water (polymer strip only)

Comments:
Sensors are reusable.
These sensors do not require a console.

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT  06070-2003

Dates of Evaluation:  11/15/93, 11/02/98

Tel:  (860) 651-2700

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.