Veeder-Root
ILS-350, TLS-300C,
300i, 300PC, 350, 350PC, 350R, 350RPC, TLS-450 Series, TLS-4 8601 Series, Red Jacket ProMax and
ProPlus
with Solid-State Pan/Sump Sensor 794380-321, 351,
Piping Sump Sensor 794380-208, 209,
Micro Sensor 794380-340
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector:
Output
type: |
qualitative |
Sampling
frequency: |
continuous |
Operating
principle: |
float/reed switch (794380-208, 209), optical (794380-321, 340, 351) |
Test
Results:
ILS-350, TLS-300C, 300i, 300PC, 350, 350PC, 350R, 350RPC, TLS-450 Series, Red Jacket ProMax and ProPlus
|
Unleaded gasoline |
Diesel* |
Water |
Used Oil |
Solid-State
Pan/Sump Sensor 794380-321, 351 |
|
|
|
|
Minimum
product level (cm) |
2.60 |
2.50 |
2.60 |
N/D**** |
Precision (cm) |
0.010 |
0.010 |
0.010 |
N/D**** |
Detection time (sec) |
<1 |
<1 |
<1 |
N/D**** |
Piping Sump Sensor 794380-208**, 209 |
|
|
|
|
Minimum
product thickness (cm) |
3.51 |
3.40 |
3.03 |
3.76 |
Precision (cm) |
0.011 |
0.011 |
0.011 |
.036 |
Detection time (sec) |
<1 |
<1 |
<1 |
<1 |
Micro
Sensor 794380-340 *** |
|
|
|
|
Minimum
product thickness (cm) |
0.51 |
0.46 |
0.48 |
N/D**** |
Precision (cm) |
0.011 |
0.007 |
0.007 |
N/D**** |
Detection time (sec) |
<1 |
<1 |
<1 |
N/D**** |
TLS-4 8601 Series
(The TLS-4 8601 Series consists of the following derivatives: TLS-4, TLS-4B, TLS-4c, TLS-4i, and TLS-S1 consoles.)
|
Unleaded gasoline |
Desel* |
Water |
Used Oil |
Solid-State
Pan/Sump Sensor 794380-321, 351 |
|
|
|
|
Minimum
product level (in) |
1.05 |
1.06 |
2.60 |
N/D**** |
Precision (in) |
0.005 |
0.04 |
0.004 |
N/D**** |
Detection time (sec) |
<1 |
<1 |
<1 |
N/D**** |
Piping Sump Sensor 794380-208**, 209 |
|
|
|
|
Minimum
product thickness (in) |
1.33 |
1.34 |
1.19 |
***** |
Precision (in) |
0.002 |
0.002 |
0.002 |
.***** |
Detection time (sec) |
<1 |
<1 |
<1 |
***** |
*Evaluations determined these sensors' responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.
**This sensor is identified as an interstitial sensor, but will function properly in other containment areas such as containment sumps, contained risers and other contained enclosures. This sensor must be installed at the lowest point of the containment enclosure to insure early detection of liquids. Results stated for used oil applicable to this sensor only.
Evaluations determined that the 794380-208 sensor responds to 100% Lubrizol Ultrazol 9888. Alarm and response can be expected to be very similar to the response values listed above.
***Micro Sensor 794380-340 is not supported by TLS 450 series console. ****See Glossary
*****TLS-4 Series testing did not include testing with used oil. Evaluator expects comparable results from previous testing with other consoles listed.
Comments:
Sensors are reusable.
TLS-4 Series testing did not include testing with used oil. Evaluator expects comparable results from previous testing with other consoles listed.
Veeder-Root
125
Powder Forest Dr.
Simsbury, CT 06070-2003
Tel:
(860) 651-2700
Email: dhalla@veeder.com URL: www.veeder.com/dynamic/index.cfm |
Evaluator: Ken Wilcox Associates
Tel:
(816) 443-2494
Dates
of Evaluations: 10/20/94, 05/22/02
, 03/03/08, 04/05/11, 12/16/16
|
|