Veeder-Root
TLS 350, 350PC,
350R, 350RPC, 350Plus, 350J, Red Jacket ProMax
Line Leak Detector, with Series 8484 PLLD and TLS 450 with Series 8590 DPLLD,
Software Version X19 or Higher (for Rigid and/or Flexible Pipelines)
AUTOMATIC ELECTRONIC LINE LEAK DETECTOR
Certification |
Leak
rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this
leak rate and pressure were certified using an equivalent
leak rate and pressure, in accordance with an acceptable
protocol.
|
Leak
Threshold |
2.0
gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold.
|
Applicability |
Gasoline, diesel, aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751*.
Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility - see "Disclaimer".
Evaluations determined that the Series 8484 PLLD responds to 100% Lubrizol Ultrazol 9888, 100% Afton OTR 8332G, and 100% Afton OTR 8843G. Alarm and response can be expected to be very similar to the response values listed above. |
Specification |
System
tests pressurized rigid, flexible, and combination of
rigid and flexible pipelines.
Tests are conducted at operating pressure.
System will not function with a mechanical line leak detector
installed in the pipeline. |
Pipeline
Capacity |
Maximum
of 212 gallons.
|
Waiting
Time |
None
between delivery and testing.
None between dispensing and testing.
|
Test
Period |
Response
time is 1 to 6 minutes.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
|
System
Features |
TLS 350 console can only be used with Series 8484 PLLD.
TLS 450 console can only be used with Series 8590 DPLLD.
When using Red Jacket BIG-FLO Submersible Pump Models P100H1, P200H1, P200H3, P300H3, P500H3, the PLLD only performs 3.0 gph testing and not precision (0.2 and 0.1 gph) testing.
{USER DEFINED} pipe type must be selected under the PLLD setup to allow precision (0.2 and 0.1 gph) testing with Red Jacket BIG-FLO Submersible Pump Models: MAXXUM MXP300, MAXXUM MXP500.
Total vertical rise of pipeline must not exceed 11 feet above transducer.
Permanent
installation on pipeline.
Automatic testing of pipeline. Preset threshold.
Single test to determine if pipeline is leaking.
Pump shutdown (optional), message display and alarm activation
if leak is declared.
|
Calibration |
Equipment
must be checked annually for capability of detecting a
line leak of 3.0 gph and, if necessary, calibrated in
accordance with manufacturer's instructions.
|
Comments |
System
was evaluated on a pipeline consisting of rigid and flexible
piping, and the resulting combined bulk modulus was determined
by physical measurement at evaluator's facility.To use
this system, a measurement of bulk modulus must be made
at the owner's facility so that the software can be programmed
to deal with specific characteristics of the piping system
at the facility. |
Veeder-Root
125 Powder Forest Dr.
Simsbury, CT 06070-2003
Tel: (860) 651-2700
E-mail: info@veeder.com
URL: www.veeder.com |
Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluation: 08/19/02, 02/27/08, 03/24/11(letter), 3/6/2013(letter), 4/4/2015 (letter)
|
|