Issue Date: November 22,
1995
Revision Date: February 22, 2017
Veeder-Root
(Originally
listed as Entropy Limited
)
Precision
Tank Inventory Control System Version 90
STATISTICAL
INVENTORY RECONCILIATION TEST METHOD (QUALITATIVE)
Certification
|
Leak
rate of 0.1 gph with PD = 97.9% and PFA = 0%..
|
Leak
Threshold
|
If
the absolute value of the calculated leak rate (gain or
loss) is less than the leak threshold and the minimum
detectable leak rate is less than or equal to 0.1 gph,
the test result is "pass." If the absolute value
of the calculated leak rate is greater than or equal to
the leak threshold, the result is "fail." If
the minimum detectable leak rate exceeds 0.1 gph and the
absolute value of the calculated leak rate is less than
the leak threshold, the test result is "inconclusive."
|
Applicability
|
Gasoline,
diesel.
Other more viscous liquids may be tested after consultation
with the vendor.
|
Tank
Capacity
|
Maximum
of 15,000 gallons..
|
Data
Requirement
|
Minimum
of 64 days of product level and flow through data.
|
Comments
|
Not
evaluated using data from manifolded tank systems.
Of 120 data sets submitted for evaluation, 13 were not
evaluated and 16 were inconclusive.
Median monthly throughput of tanks evaluated was 42,835
gallons.
Data sets evaluated were supplied by evaluator.
This method does not meet the Federal UST requirement for Statistical Inventory Reconciliation to report a quantitative result with a calculated leak rate. (40 Code of Federal Regulations, part 280.43(h)(1).)
|
Gilbarco/Veeder-Root
|
Evaluator: Midwest Research Institute
|
Attn:
CMS Mailstop F-76
|
Tel: (816) 753-7600
|
7300
West Friendly Ave.
|
Date
of Evaluation: 04/02/91
|
P.O.
Box 22087 |
|
Greensboro,
NC 27420-2087 |
|
Tel: (800) 253-8054
|
|
|