Issue
Date: November 22, 1995
Revision Date: September 20, 2011
Veeder-Root
(originally listed as Marley Pump Co.)
Red
Jacket DLD, XLD
AUTOMATIC
MECHANICAL LINE LEAK DETECTOR
Certification
|
Leak
rate of 3.0 gph with PD = 100% and PFA = 0%.
|
Leak
Threshold
|
2.0
gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold.
|
Applicability
|
Gasoline, diesel, aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751*.
Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility - see "Disclaimer".
|
Specification
|
System
tests pressurized fiberglass and steel pipelines.
Tests are conducted at 8-12 psi.
|
Pipeline
Capacity
|
Maximum
of 129 gallons.
|
Waiting
Time
|
None
between delivery and testing.
None between dispensing and testing.
|
Test
Period
|
Response
time is 6 seconds.
|
System
Features
|
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared.
|
Calibration
|
Equipment
must be checked annually for capability of detecting a
line leak of 3.0 gph and, if necessary, calibrated in
accordance with manufacturer's instructions.
|
Veeder-Root
|
Evaluator: Ken Wilcox Associates
|
125
Powder Forest Dr.
|
Tel: (816) 443-2494
|
Simsbury, CT 06070-2003
|
Dates
of Evaluation: 12/21/90, 03/24/11(letter)
|
Tel: (860) 651-2700
|
|
E-mail: info@veeder.com |
|