Issue
Date: July 31, 2001
Revision Date: September 20, 2011
Veeder-Root
(originally listed as Marley Pump Co.)
Red
Jacket FX1DV, FX2DV Installed in the Big-Flow
(for Flexible Pipelines)
AUTOMATIC
MECHANICAL LINE LEAK DETECTOR
Certification
|
Leak
rate of 3.0 gph with PD = 100% and PFA = 0%.
|
Leak
Threshold
|
2.0
gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold.
|
Applicability
|
Diesel, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751*.
Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility - see "Disclaimer".
|
Specification
|
System
tests pressurized flexible pipelines.
Tests are conducted at operating pressure.
|
Pipeline
Capacity
|
Maximum
of 39.4 gallons.
|
Waiting
Time
|
None
between delivery and testing.
None between dispensing and testing.
|
Test
Period
|
Response
time is less than 3 minutes.
|
System
Features
|
Permanent
installation on pipeline.
Automatic hourly testing of pipeline.
Preset threshold.
Total vertical rise of pipeline must not exceed 11 feet above leak detector.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared.
|
Calibration
|
Equipment
must be checked annually for capability of detecting a
line leak of 3.0 gph and, if necessary, calibrated in
accordance with manufacturer's instructions.
|
Veeder-Root
|
Evaluator: Ken Wilcox Associates
|
125 Powder Forest Dr.
|
Tel: (816) 443-2494
|
Simsbury, CT 06070-2003
|
Dates
of Evaluation: 03/15/94,
07/30/96, 03/11/99, 03/24/11(letter)
|
Tel: (860) 651-2700
|
|
E-mail: info@veeder.com |
|
URL: www.veeder.com |
|
|