SIR 1.91
STATISTICAL
INVENTORY RECONCILIATION TEST METHOD (QUANTITATIVE)
Certification
|
Leak
rate of 0.1 gph with PD = 98.4% and PFA = 1.6%.
"If a method meets the requirement for detecting
a leak rate of 0.1 gph, it will meet the requirement for
0.2 gph.", according to "Standard Test Procedures
for Evaluating Leak Detection Methods: Statistical
Inventory Reconciliation Methods", EPA/530/UST-90/007,
June 1990, Section 7.2.3, page 30.
|
Leak
Threshold
|
If
the absolute value of the calculated leak rate (gain or
loss) is less than the leak threshold and the minimum
detectable leak rate is less than or equal to 0.1 gph,
the test result is "pass." If the absolute value
of the calculated leak rate is greater than or equal to
the leak threshold, the result is "fail." If
the minimum detectable leak rate exceeds 0.1 gph and the
absolute value of the calculated leak rate is less than
the leak threshold, the test result is "inconclusive."
|
Applicability
|
Gasoline,
diesel.
Other more viscous liquids may be tested after consultation
with the vendor.
|
Tank
Capacity
|
Maximum
of 18,000 gallons.
|
Data
Requirement
|
Minimum
of 42 days of product level and flow through data.
|
Comments
|
Not
evaluated using data from manifolded tank systems.
Of 41 data sets submitted for evaluation, 4 data sets
were not analyzed and 7 were inconclusive.
Median monthly throughput of tanks evaluated was 10,978
gallons.
Leak rates ranging from 0.048 to 0.201 gph were used in
evaluation.
Data sets evaluated were supplied by evaluator.
|