Issue Date: August 15, 2022

Franklin Fueling Systems

EVO 600 and EVO 6000
Consoles with FMP-DIS Discriminating Interstitial Sensor and FMP-EIS Electro-Optical Interstitial Sensor

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Conductivity, electro-optic

Test Results

  Unleaded Gasoline Diesel* Waste oil Water E85
FMP-DIS
Detection time (min) <1 <1 <1 <1 <1
Fall time (min) <1 <1 <1 <1 <1
Threshold level (in) 0.2996 0.3057 0.2934 0.3134 0.2886
FMP-EIS
Detection time (min) <1 <1 <1 <1 <1
Fall time (min) <1 <1 <1 <1 <1
Threshold level (in) 0.2718 0.2728 0.2534 0.2792 0.2700

Applicability

California Code of Regulations require a written statement of compatibility for systems containing products other than those used in this evaluation.

Comments

Sensors can be removed, cleaned, and reinstalled if an alarm is triggered or if the sensor is periodically tested.

The FMP-DIS and FMP-EIS sensors are identical in operation and communication to Franklin Fueling System’s TSP-DIS and TSP-EIS sensors. The FMP-DIS and FMP-EIS sensors can connect to any INCON console with no software or setup changes. FMP-DIS and FMP-EIS sensors can be distinguished from TSP-DIS and TSP-EIS sensors by the part number on the label that begins with “FMP” instead of “TSP.” The TSP-DIS, TSPEIS, FMP-DIS and FMP-EIS sensors appear as the same device from the automatic tank gauge.

The FMP-DIS sensor uses two conductive pins to detect whether the liquid is water or fuel. When tested in three mixtures of water/E85 (i.e., 20%/80%; 30%/70%; and 70%/30%), the FMP-DIS sensor went into alarm when subjected to the upper and lower layers of water/E85. For the upper layer containing hydrocarbon, the DIS sensor indicated a product or alarm as designed. For the lower layer of liquid, the DIS sensor indicated a “water” alarm.

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.