Issue Date: March 11, 2011

Preferred Utilities Manufacturing Corporation

TG-EL-D4A Fuel Sentry Control Unit, HD-A2-C Optical Discriminating Sensor

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Optical Sensor

Test Results

  Unleaded Gasoline Diesel* Water
Detection time (sec) <5 <5 <5
Fall time (sec) <5 <5 <5
Lower detection limit (in) 0.125 0.125 0.125

Comments

Control panel: Six intrinsically safe sensor inputs can be used for level indication and/or leak detection. Provides audible and visual alarms.

Sensor: Primarily designed for use with diesel fuel and other distillates but can be used with other fluids - see manufacturer for specific limitations.

*This evaluation determined the sensors' responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Used to detect the presence of liquids in fiberglass and steel tank annular spaces or the presence of liquids in tank vault spaces.
Can also be used for detection of leaks into sumps or other containment vessels used to collect liquids.

  • Preferred Utilities Manufacturing Corporation
    31-35 South Street
    Danbury, CT 06810
    Tel: (203) 743-6741
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 6/17/10

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.