Tanknology - NDE
TLD-1
Line Tightness Test Method
Certification | Leak rate of 0.1 gph with PD = 99.5% and PFA = 0.5%. |
---|---|
Leak Threshold | 0.05 gph. A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold. |
Applicability | Gasoline, diesel, aviation fuel. |
Specification | System tests fiberglass and steel pipelines. Tests are conducted at 150% operating pressure. Mechanical line leak detector must be removed or manually isolated from pipeline for duration of test, or check valve in pump must be manually closed if testing is to be conducted with mechanical line leak detector in place. |
Pipeline Capacity | Maximum of 172 gallons. |
Waiting Time | Testing may begin immediately after system is installed in the line. |
Test Period | Response time is 30 minutes to 6 hours. Test may not be ended until pass/fail criteria set by manufacturer has been met. Pipe deflection, vapor pockets, and large temperature differences may produce inconsistent readings. Testing must continue until stable conditions are present. Test data are acquired and recorded manually. |
- Tanknology - NDE
8900 Shoal Creek Blvd., Building 200
Austin, TX 78757
Tel: (800) 800-4633 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 12/29/91, 03/04/02
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.