Issue Date: August 23, 1999
Revision Date: December 16, 2015
Vaporless Manufacturing
Vaporless 98LD-2000, 99LD-2000, 99LD-2200, LD-2200 Scout (for Rigid and Flexible Pipelines)
Automatic Mechanical Line Leak Detector
Certification | Leak rate of 3.0 gph with PD = 100% and PFA = 0%. |
---|---|
Leak Threshold | 2.5 gph. A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold. |
Applicability | Gasoline, diesel, aviation fuel. Evaluations determined that the 99LD-2000 MLLD responds to 100% Lubrizol Ultrazol 9888, 100% Afton OTR 8332G, and 100% Afton OTR 8843G. Alarm and response can be expected to be very similar to the response values listed above. |
Specification | System tests pressurized flexible, fiberglass, and steel pipelines. Tests are conducted at operating pressure. |
Pipeline Capacity | Maximum of 172 gallons for rigid pipelines. Maximum of 39.5 gallons for flexible pipelines. |
Waiting Time | None between dispensing and testing. None between delivery and testing. |
Test Period | Response time is less than 1 minute without a leak and 1 to 8 minutes with a leak. |
System Features | Permanent installation on pipeline. Automatic testing of pipeline. Preset threshold. Single test to determine if pipeline is leaking. Restricted flow to dispenser if leak is declared. |
Calibration | Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments | Functionality and operability of the 99 LD-2000 and 99 LD-2200 are unchanged by installation of the Leak Detection Sensor (piston switch) that supports the VMI ISM-4080 and ISM-4081 Integrated Shutdown Module. |
- Vaporless Manufacturing
8700 East Long Mesa Drive
Prescott Valley, AZ 86314
Tel: (520) 775-0185 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluation: 05/20/98, 11/10/98 , 12/9/15
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.